The three formulas
For direct current, power is simply voltage times current: P = V × I. A 12 V lamp drawing 5 A uses 60 W.
For single-phase AC — ordinary household sockets — the same product is multiplied by the power factor: P = V × I × PF. The power factor is the share of the current that does useful work. For a purely resistive load such as a kettle, an electric heater or an incandescent bulb, voltage and current rise and fall together and the power factor is 1, which is why the calculator starts there. Motors, compressors and many power supplies draw current that is out of step with the voltage, so their power factor is lower — often somewhere between 0.6 and 0.95 — and they draw more amps for the same watts.
For three-phase AC the formula gains a factor of √3 (about 1.732): P = √3 × V × I × PF, where V is the line-to-line voltage — the voltage measured between two phases, such as 400 V in Europe or 208 V and 480 V in North America. Using the line-to-neutral voltage here instead gives a current √3 times too high.
Watts, volt-amperes and kilowatts
Watts measure real power, the energy actually used. Volt-amperes (VA) are simply volts times amps (times √3 on three-phase) and measure apparent power — what the wiring and supply have to carry. The two are equal when the power factor is 1. Generators and UPS units are often rated in VA or kVA for that reason. Watts to kilowatts is a plain division by 1,000: 1,500 W is 1.5 kW. The calculator shows every figure in both.
What it does not do
Knowing the current a load draws is the start of choosing a cable or breaker, not the end. Cable size also depends on its length, how it is installed and bundled, the ambient temperature and the allowed voltage drop, and breakers are chosen with safety margins your local electrical code sets. Use this to understand the numbers, and ask a qualified electrician to design anything you will connect to the mains.